Here are two clues that will help you plan for installing the new Dell server families.
They seem to be great servers... lots of capacity for RAM, lots of CPU strength, and I love the rack mounting rail system. I also like the iDRAC service processors.
What's not to like? The back of the chassis is too thick (or the DE9 console port is recessed too far). Either way, most of the serial console adapters (DE9 to RJ45) won't fit well, and provide reliable connections, unless you grind down the cases of the adapters. And, since the adapter vendors don't offer to sell you a "trimmed" version, that job is going to cost you extra, somehow. Hey, maybe we can get the intern to do it? ;-)
I'm *really* glad that the serial consoles are still on the back of the servers, but if you are going to put them there, it seems to me that making the serial adapters fit should be part of the plan to have them on the server.
The one adapter I've found that works on the R620 series servers is from Cyclades (ADB0036). Yes, you can still get them from CDW. Fortunately, our latest batch went into racks with Cyclades TS2000. But, I did need to modify SO MANY of the Lantronix adapters that I made a custom jig for a Dremel router, to get consistent results.
Clue number two: On the R620, ttyS0 goes tot he iDRAC, and ttyS1 goes to the DE9 on the rear of the server. You will need to start an agetty for BOTH of these, if you want to be able to use both of them.
My other big projects are nearly done, and I plan to post much more often this summer. Thanks for reading.
Showing posts with label consoleteam. Show all posts
Showing posts with label consoleteam. Show all posts
20090522
Look at all the pretty lights
This week, I needed to reconfigure a previously-used Cyclades ACS console server. Finding the right adapters was easy enough, but getting the USB serial dongle to play was the tricky bit. Without a signal tracer, I was stuck with the evidence... "it's not working"...and I was trying different hardware combinations, and a few software changes. I wasted 2.5 hours going through different combinations, and I put a reminder in my calendar to bring my signal tracers and my Serial Doctors Bag the next day.
Once I had my trusty signal tracers, it was a matter of 10 minutes to find the proper USB settings, COM port configuration in my terminal emulator, and start the reconfiguration process. Blinky lights will save you time, every time. Good quality signal tracers are worth a high cost, because they will save you time often, and serve you well for many years. One day, blinky lights will probably save my life...
So, having solved Problem #1, and with kit in hand, I tackled Problem #2;
Years ago, a couple of hundred APC smart power strips (OK, "0-RU, metered Power Distribution Units") were installed in a data center. Fast forward to last week, when one unit is failing to respond to SNMP after a high-temperature 'event' in the room. Since it was in critical service, we wanted to try using the serial console to see if the brains were still alive. Unfortunately, nobody could find a serial cable for the job, and APC doesn't want folks making their own cables so APC doesn't post any signaling clues. I did find one website with clues about the wiring for the 940-0144 cable.
The clues indicated that the 6-pin RJ-14 interface was, indeed, RS-232 (and not TTL, for example), I could do some experimenting. A new toy in my Doctors Bag (not in the pictures (yet), is a MODAPT from Siemon. With this, and my trusty Digital Volt Meter (DVM), I was able to confirm some signalling that wasn't mentioned in the LuxNET web page.
I'll update my APC console page and my Signals page soon with some of this information.
Once I had my trusty signal tracers, it was a matter of 10 minutes to find the proper USB settings, COM port configuration in my terminal emulator, and start the reconfiguration process. Blinky lights will save you time, every time. Good quality signal tracers are worth a high cost, because they will save you time often, and serve you well for many years. One day, blinky lights will probably save my life...
So, having solved Problem #1, and with kit in hand, I tackled Problem #2;
Years ago, a couple of hundred APC smart power strips (OK, "0-RU, metered Power Distribution Units") were installed in a data center. Fast forward to last week, when one unit is failing to respond to SNMP after a high-temperature 'event' in the room. Since it was in critical service, we wanted to try using the serial console to see if the brains were still alive. Unfortunately, nobody could find a serial cable for the job, and APC doesn't want folks making their own cables so APC doesn't post any signaling clues. I did find one website with clues about the wiring for the 940-0144 cable.
The clues indicated that the 6-pin RJ-14 interface was, indeed, RS-232 (and not TTL, for example), I could do some experimenting. A new toy in my Doctors Bag (not in the pictures (yet), is a MODAPT from Siemon. With this, and my trusty Digital Volt Meter (DVM), I was able to confirm some signalling that wasn't mentioned in the LuxNET web page.
Pin1 -2v (in reference to Pin2)
Pin2 GND (0v potential to Pin5)
Pin3 TxD output (-5.5v in reference to Pin2)
Pin4 RxD input (0.2V in reference to Pin2)
Pin5 GND (0v potential to Pin2)
Pin6 -2v (in reference to Pin2)
I'll update my APC console page and my Signals page soon with some of this information.